The DCA45SSIU4F offers a prime rating of 36 kW (45 kVA) and a standby rating of 40 kW (50 kVA).
Our patented open delta generator winding provides precise voltage control, allowing superior motor starting capability. An electronic governor maintains frequency to ± 0.25% from no load to full load. It features an auto start stop that allows the generator to start from a remote location.
The unit features an e-coat and powder-coated, weatherproof steel housing that allows a substantially low operating noise level of 66 dB(A). Â A comprehensive analog control panel provides instrumentation including AC ammeter, AC voltmeter, frequency meter, AC circuit breaker, engine gauges and much more.
- Heavy duty, 4-cycle, direct injection, heated crankcase vent, turbocharged, charge air cooled, diesel engine provides maximum
- EPA emissions certified Tier 4 Final emissions
- Microprocessor engine control system maintains frequency to ±0.25%.
- Full load acceptance of standby nameplate rating in a single
- Fuel/water separator removes condensation from fuel for extended engine Panel-mounted alarm light included.
- Sound attenuated, weather resistant, steel housing provides operation at 66 dB(A) at 23 Fully lockable enclosure allows safe unattended operation.
- E-coat and powder coat paint provide durability and weather
- Internal fuel tank with direct reading fuel
- Spill containment —Bunded design protects environment by capturing up to 119% of engine
- Brushless alternator reduces service and maintenance requirements and meets temperature rise standards for Class H insulation
- Open delta alternator design provides virtually unlimited excitation for maximum motor starting
- Automatic voltage regulator (AVR) provides precise
- Fully covered power Three-phase terminals and single-phase receptacles allow fast and convenient hookup for most applications including temporary power boxes, tools and lighting equipment. The GFCI receptacles are NEMA 5-20, and the auxiliary outputs use CS6369 twist-lock receptacles.
- ECU754 microprocessor-based digital generator
- Remote 2-wire start/stop
- Operational temperature range of -40° to 85°
- Digital engine gauges including oil pressure, water temperature, battery volts, engine speed and fuel level.
- Analog generator instrumentation including AC ammeter, AC voltmeter, frequency meter, ammeter phase selector switch, voltmeter phase selector switch, and voltage regulator adjustment
- Automatic safety shutdown system monitors the water temperature, engine oil pressure, overspeed, and over crank. Warning lights indicate abnormal
Emergency Stop Switch — when manually activated, shuts down generator in the event of an emergency.