Sell

install

Cummins C30D6 30kW Diesel Generator Sound Level 1 Enclosure 120/240 1Ph-no tank Backup Generator A063P964

Cummins C30D6 Pre-Configured 30kW Diesel Generator Sound Level 1 Enclosure 120/240 1Ph-no fuel tank – A063P964

The generator is designed to operate under extreme environmental conditions. The generator is tested and certified per the latest EPA and UL standards.

$18,242.22

questions? Call US

(866) 888 6111

SKU: 300618 Category:

Accessories

CALL US AT 866-888-6111 FOR A FULL LIST OF ACCESSORIES OFFERED FOR THIS PRODUCT!!

Loading...

Description

Cummins C30D6 Pre-Configured 30kW Diesel Generator Sound Level 1 Enclosure 120/240 1Ph-no fuel tank – A063P964

The generator is designed to operate under extreme environmental conditions. The generator is tested and certified per the latest EPA and UL standards.

Additional information

Weight 1382 lbs
Dimensions 105.8 × 46 × 57.5 in
Product Applications

Commercial / Industrial Power, Residential

Capability

Install, Sell, Service

Cooling System

Liquid Cooled

Certification

UL

Manufacturer

Cummins

MPN

A063P964

Frequency Hz

60

Fuel Type

Diesel

Power Type

Conventional

Phase AC

1PH

Watts

30000

kW

30

Voltage VAC

120/240

Gen/Power Rating

Standby / Intermittent

Housing

Closed

kVA

30

VA

30000

Reviews

There are no reviews yet.

Be the first to review “Cummins C30D6 30kW Diesel Generator Sound Level 1 Enclosure 120/240 1Ph-no tank Backup Generator A063P964”

Your email address will not be published. Required fields are marked *

Tech Notes

Generator set specifications

Engine QSB3.3

Enclosures Sound Level 1 – Sandstone

Controller PowerCommand 1.1

Voltage – Phase 120/240 – 1 Phase

Operating temp. range -40 °F to +122 °F (-40 °C to +50 °C)

Circuit Breaker 100 

Battery Charger Standard – 6A

Governor reg. class ISO 8528 Part 1 Class G3

Voltage regulation, no load to full load ± 1.0%

Random voltage variation ± 1.0%

Frequency regulation Isochronous

Random freq. variation ± 0.5%

Radio frequency emissions compliance FCC code Title 47 part 15 class A and B 

Engine specifications 

Engine QSB3.3  

Displacement 3.40 L(199.1 in)

Cylinder block Cast iron, in-line

Battery capacity at ambient temperature of 0 °C (32 °F) 550 amps 

Battery charging alternator 40 amps 

Starting voltage 12-volt, negative ground

Lube oil filter type(s) Spin-on with relief valve

Rated speed 1800 rpm 

Alternator specifications

Design Brushless, 4 pole, drip proof, revolving field 

Stator 2/3 pitch

Rotor Direct coupled, flexible disc

Insulation system Class H per NEMA MG1-1.65

Standard temp. rise 120 ºC (248 °F) Standby

Exciter type Torque match (shunt) with PMG as option

Alternator cooling Direct drive centrifugal blower

AC waveform Total Harmonic

Distortion (THDV) < 5% no load to full linear load, < 3% for any single harmonic

Telephone Influence Factor (TIF) < 50 per NEMA MG1-22.43

Telephone Harmonic Factor (THF) < 3% 

Dimensions and Weight