Sell

install

Cummins C100D6C 100kW Diesel Generator Sound Level 1 Enclosure 120/240 1Ph-24hr tank Backup Generator A063P977

Cummins C100D6C Pre-Configured 100kW Diesel Generator Sound Level 1 Enclosure 120/240 1Ph-24hr basic tank – A063P977

The generator is designed to operate under extreme environmental conditions. The generator is tested and certified per the latest EPA and UL standards.

$36,948.77

questions? Call US

(866) 888 6111

SKU: 300626 Category:

Accessories

CALL US AT 866-888-6111 FOR A FULL LIST OF ACCESSORIES OFFERED FOR THIS PRODUCT!!

Loading...

Description

Cummins C100D6C Pre-Configured 100kW Diesel Generator Sound Level 1 Enclosure 120/240 1Ph-24hr basic tank – A063P977

The generator is designed to operate under extreme environmental conditions. The generator is tested and certified per the latest EPA and UL standards.

Additional information

Weight 3409 lbs
Dimensions 131 × 52 × 95 in
Product Applications

Commercial / Industrial Power, Residential

Capability

Install, Sell, Service

Cooling System

Liquid Cooled

Certification

UL

Manufacturer

Cummins

MPN

A063P977

Frequency Hz

60

Fuel Tank Run Time (hrs)

24

Fuel Type

Diesel

Power Type

Conventional

Phase AC

1PH

Watts

100000

kW

100

Voltage VAC

120/240

Gen/Power Rating

Standby / Intermittent

Housing

Closed

kVA

100

VA

100000

Reviews

There are no reviews yet.

Be the first to review “Cummins C100D6C 100kW Diesel Generator Sound Level 1 Enclosure 120/240 1Ph-24hr tank Backup Generator A063P977”

Your email address will not be published. Required fields are marked *

Tech Notes

Generator set specifications

Engine QSB5  

Enclosures Sound Level 1 – Sandstone

Controller PowerCommand 1.1

Voltage – Phase 120/240 – 1 Phase

Operating temp. range -40 °F to +122 °F (-40 °C to +50 °C)

Circuit Breaker 100 

Battery Charger Standard – 6A

Governor reg. class ISO 8528 Part 1 Class G3

Voltage regulation, no load to full load ± 1.0%

Random voltage variation ± 1.0%

Frequency regulation Isochronous

Random freq. variation ± 0.5%

Radio frequency emissions compliance FCC code Title 47 part 15 class A and B 

Engine specifications 

Engine QSB5  

Displacement 4.50 L(272 in)

Cylinder block Cast iron, in-line

Battery capacity at ambient temperature of 0 °C (32 °F) 2×850 amps 

Battery charging alternator 100 amps 

Starting voltage 2x 12-volt, negative ground

Lube oil filter type(s) Spin-on with relief valve

Rated speed 1800 rpm 

Alternator specifications

Design Brushless, 4 pole, drip proof, revolving field 

Stator 2/3 pitch

Rotor Direct coupled, flexible disc

Insulation system Class H per NEMA MG1-1.65

Standard temp. rise 120 ºC (248 °F) Standby

Exciter type Torque match (shunt) with PMG as option

Alternator cooling Direct drive centrifugal blower

AC waveform Total Harmonic

Distortion (THDV) < 5% no load to full linear load, < 3% for any single harmonic

Telephone Influence Factor (TIF) < 50 per NEMA MG1-22.43

Telephone Harmonic Factor (THF) < 3% 

Dimensions and Weight

Downloads

You may also like..

Related articles and tips

There are no related articles to this product